Suggested Mounting of Level Sensors (Transducers):
There are many ways to mount transducers. Shown below is the
simplest way. Drill hole in the tank opening flange and tap the hole with 3/4
inch NPT female thread. Our transducer threads in. The transducer cable should
be placed in conduit, to protect it from elements.
![]() |
![]() |
Standard transducers 7508
and 2006 will fit 2 inch opening.
Transducers 4012A, 4012BS (316 stainless steel) and
4012BS/CSA (stainless steel
explosion-proof) fit 3 inch opening. We have several other transducer models to
fit smaller openings.
For liquid monitoring applications, transducer should be
mounted vertical. It does not have to be in the tank center. However,
the transducer should not
be positioned in front of the inlet pipe or too close to the tank wall. As a
rule of thumb, the minimum distance from the wall should be 10 % of the tank
height, assuming the wall is relatively smooth. For tanks 20
ft. or higher, two to three feet distance would be
adequate.